SENSOR REPLACEMENT
GENERAL: The Twin Toxic, Oxygen and the Combustible sensors have a two
(2) year warranty. Sensors should be replaced at the end of their warranty period.
Replace dirty or plugged sensors immediately. Failure to do so may compromise the
unit's effectiveness as a safety instrument.
SENSOR PLACEMENT: With the LCD (front of the BW DEFENDER) facing you:
Oxygen Sensor (Black band) - Left hand side (nearest the battery)
(2 year: # O2-A2) (1 year: # O2-A1)
Twin Toxic Sensor (Turquoise band) - Middle Sensor
Combustible Sensor (Silver sensor) - Right hand side
NOTE: Leave the shorting wire across the pins of the Twin Toxic sensor until just
before installation.
1. With the BW DEFENDER turned OFF, remove the 4 screws on the top endcap.
Remove the top endcap and the replaceable sensor screens.
2. Using a pair of needlenose pliers or similar tool, grasp the desired sensor firmly
and pull straight out. Rocking the sensor back and forth gently may help free
tightly held sensors. Do not use excessive force or sensors may be crushed.
3. Line up and insert the replacement sensor. It fits one way only. Push firmly into
the mating sockets. Do not force into place. When fully seated, all sensors will be
approximately the same height.
4. Replace the endcap and sensor screens with the 4 screws. Tighten the screws
only slightly more than finger tight.
5. Turn the BW DEFENDER ON for 30 minutes and then calibrate the monitor. (See
“CALIBRATION”.)
UPGRADING: 2-gas BW DEFENDERs may be upgraded to a 4-gas BW DEFENDER
in the field with the D4-UPGRADE1 Kit.
SENSOR STORAGE: Sensors should be stored in a cool place (0 to 20°C
(32 to 68°F)). Keep in the sealed container they were shipped in.
DEACTIVATING THE DETECTOR
GENERAL: The BW DEFENDER “OFF” function is designed to prevent accidental
shut off, and will warn you that the BW DEFENDER is being shut down.
1. To deactivate, press the (ON/OFF) key
firmly and hold it down until the word “OFF”
appears on the screen (approximately
4 seconds).
OFF WARNING: Prior to the “OFF” readout
the detector will emit 4 beeps and flash the
alarm LEDs as a warning that the unit will
be shutting down. Shut down will occur
after the word “OFF” displays.
NOTE: If the button is released before
4 seconds have elapsed, the unit will not
shut off. If this happens accidentally: Press
the key again for 4 seconds.
BACKLIGHT DISPLAY
Access the BW DEFENDER LCD backlight
feature to view the display in poor light.
The backlight will remain lit for about
5 seconds, and then automatically shut off.
1. Press and release the TAB key.
# The backlight is automatically activated if
any gas alarm condition exists.
NOTE: If the key is held down over 5 seconds,
the TWA and Peak Exposure information
will be displayed. (See “Accumulated
Exposure Levels”.) The backlight will
deactivate automatically after the TWA
information is finished displaying.
Tab
9
26
Updated Nov, 2000 English D1218/3 Page 26 (take out one (1) year O2 warranty in first paragraph; distinguish 1 yr vs.2 yr.O2 sensor)
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 39 40

Comments to this Manuals

No comments